Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM01334

Parcel: 128100530

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/24/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) OK FOR FINAL C OF O
05/23/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE FUSES IN ELECTRIC DISCONNECTS
2) PERMANENTLY LABEL CONDENSOR WITH ADDRESS/SUITE NUMBER
3) PROVIDE A DRIP LEG ON REFER LINES