Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/12/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NEED 2" CLEAR TO FIREPLACE VENT 2) BLOCK A/C REGISTERS |
|
| 07/11/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) BLOCK A/C REGISTERS 2) NEED 1 1/2 CLEARANCE TO FIREPLACE VENT 3) CHECK STAPLING EAST SIDE 4) COMPLETE POP-OUTS AND CAULKING 5) BOX FOR WATER HEATER WIRE 6) WIRE TOILET EXHAUST FAN 7) ADD RECEPTACLE NORTH WALL MASTER BEDROOM 8) PURPOSE OF LOOSE WIRE IN DINING ROOM 9) RAISE HALL S/D TO BETWEEN 6 + 12 INCHES OF CEILING 10) INSTALL FURNACE DISCONNECT 11) NO DWV TEST 12) PEX NEEDS 12" CLEARANCE TO CAN LIGHTS 13) NO PRESSURE TEST ON PEX |