Permit: T05CM01324

Parcel: 11706168C


Addresses:

318 E CONGRESS ST


Inspection Status: Approved

Inspection History: ELECTRIC - PROGRESS

Permit Number - T05CM01324

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2007 ELECTRIC - PROGRESS Approved
08/10/2006 ELECTRIC - PROGRESS Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/14/2005 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
04/05/2005 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :* NOTES: 1) REVISE PLANS FOR LIGHTING, POWER CHANGES. 2) SUPPORT MC CABLE IN ATTIC PER NEC. WITHIN 12" OF TERMINATION & AT 6' INTERVALS. 3) OK CONDUITS IN & CAN LTS IN HARD CEILING IN LOBBY