Permit: T05CM01299

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/01/2005 FRAMING Approved IVRS - Inspection :*
08/30/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STUCCO LATH NOT COMPLETE AT BACK PORCH
2) BUILT UP POST REQUIRED UNDER GLUE LAM BEAM NORTH END
3) 1" CLEARANCE REQUIRED TO COMBUSTABLE MATERIAL (ABS PLASTIC)
4) FIRE STOP REQUIRES 2 LAYERS OF 1/2" OSB
5) FIRE STOP W/H VENT CHASE AT 2ND FLOOR CEILING
6) FIRE STOP EAST CHASE AT GARAGE
7) 2ND FLOOR P.1 SHEAR WALL SILL PLATE NOT NAILED PER PLAN
8) FIRE STOP 2ND FLOOR PENETRATING
9) ANCHOR WALLS
10) HOLD DOWNS MISSING, SEE PLAN
11) LEAK AT DWV STACK WYE
12) CLIP BEARING POSTS TO PLATE
13) STRAINED / MIS ALIGNED DOWN CONNECTION AT KITCHEN
DIRTY ARM
14) AC WIRES OUT OF WALE?