Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 05/25/2005 | ELECTRIC - CABLE DROP | Denied | NO RISER |