11/23/2005 PLUMBING - ABOVE CEILING Approved IVRS - Inspection :*
11/16/2005 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ALL DRAINS FROM BACKFLOW DEVICES TO TERMINATE WITH 90 DEGREE DOWN AT FLOOR SINKS
2) REPAIR LEAKS AT DRAINS ON BACKFLOW THAT ARE DUMPING WATER
3) PERM CAP OLD DRAIN IN RESTROOM
4) DRAINS FROM FOOT SPA'S TO BE DIRECTIONAL FITTING WITH NO RESTRICTION AND GRAVITY DRAIN
5) CHAIR #4 TO HAVE GRAVITY DRAIN AND TERMINATE AT DOWNWARD ANGLE WITH 1" AIR GAP
6) SUPPORT VENT ABOVE CEILING IN BREAK ROOM
7) DRAINS FROM BACKFLOWS TO GRAVITY DRAIN AND BE SUPPORTED AT 4' INTERVALS