Permit: T05CM01287

Parcel: 13623007Y


Addresses:

2712 S KOLB RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM01287

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*WATER TEST UNDERGROUND WASTE & VENT THRU ROOF OK
10/27/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*PROVIDE WATER TEST ON UNDERGROUND PIPING
INSTALL WASTE & VENT PER PLAN
INSTALL H20 PIPING PER PLAN
WATER HEATER T & P TO GRAVITY DRAIN TO DAYLIGHT OR APPROVED RECEPTOR
PLUMBER CONTRACTOR TO BE ON SITE FOR NEXT INSPECTION
PROVIDE SUPPORTS FOR ALL DRAIN PIPING AT CORRECT INTERVALS WITH 1" AIR GAP
05/11/2005 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) 8 FOOT SPA'S INSTALLED WITHOUT PERMITS AND INSPECTIONS. SINK RELOCATED, WASHING MACHINE BOX DRAIN AND H20 ADDED
2) PROVIDE PIPING PER YOUR APPROVED PLANS WITH INSPECTION AND TESTING
3) EXPOSE WASTE AND VENT AT NEW FLOOR SINK LOCATIONS UNDER CHAIRS WHEN FLOOR SINKS ARE BEING INSTALLED
4) INSTALL H20 PIPING PER PLAN WITH BACKFLOW PROTECTION REQUIRED PER PLAN
5) WATER HEATER TEMPERATURE AND PRESSURE RELIEF TO GRAVITY DRAIN TO DAY LIGHT
6) EXPOSE P-TRAP AT WASHING MACHINE DRAIN FOR INSPECTION
7) EXPOSE SINK CLEANOUT AT P-2 LOCATION
8) PROVIDE POSSIBLE CAMERA VIEWING OF MAIN SEWER IF NECESSARY
9) EXPOSE VENT PIPING TO VERIFY SIZING OF VENT AND TERMINATION THRU ROOF
10) DEPENDING ON SIZING OF BLDG DRAIN WHAT IS VIEWED AT NOTE #3, 6 AND 7 WHEN VIEWING IS MADE POSSIBLE, ADDITIONAL TESTING AND INSTALLING OF CORRECT PIPING FOR APPROVED PLAN WILL BE REQUIRED