Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/06/2005 |
ELECTRIC - ABOVE CEILING |
|
Approved |
IVRS - Inspection :* |
| 05/16/2005 |
ELECTRIC - ABOVE CEILING |
|
Partial Approval |
IVRS - Inspection :* CK ON FINAL PLEASE LEAVE AREAS OPEN AS DISCUSSED |
| 05/13/2005 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection :* 1) FIXTURES TO BE ATTACHED TO GRIP 410.16. 2) FINISH BOX MAKE UP 3) M/C CABLE TO BE SUPPORTED AS PER 300.11 AND 330.13. 4) VDV CABLEING TO BE AS PER 725.6 & 800.6. 5) PLEASE PROTECT VDV CABLEING FROM SHARP METAL EDGES. |