Permit: T05CM01258

Parcel: 140383000

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/28/2005 FRAMING Approved IVRS - Inspection :*
SEE ITEM OF 7/22/05 INSPECTION - OK TO INSULATE & DRY IN
07/27/2005 FRAMING Partial Approval IVRS - Inspection :*
07/26/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
07/22/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE ENGINEERING LETTER DATED 7/11/05 APPROVED BY CITY FOR THIS ADDRESS
2) PROVIDE LSI CERTIFICATION OF 3000 PSI CONCRETE IN REPAIR
3) NO DWV WATER TEST
4) SHIM HEADERS TO DBL TOP PLATES (SAGGING)
5) DUCT RESTRICTED BR 3
07/20/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO DWV WATER TEST
2) FIRE/SHEAR BLOCK MISSING GARAGE/LAUNDRY
3) SHIM HEADER TO TRIMMERS
4) PEX CANNOT BE WITHIN 12" OF CAN LIGHTS
5) AC DUCT MISSING M. BATH
6) PLUMBING OUT OF WALL M. LAV
7) W/C REQUIRES 15" TO WALLS
8) PROVIDE 1/2" TRUSS CLEARANCE
9) LAV DIRTY ARM CANNOT EXCEED 1 1/2"
10) RED HEADS LOOSE
11) DUCTS RESTRICTED
12) GAS LINE MUST BE WITHIN 36" OF FURANCE
13) HAVE ENGINEERING CITY OF TUCSON APPROVAL