Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/07/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 4, 5, 6, 7, 9, 10, AND 14) NOT DONE 7) SECURE PORCH OUTLET 9, 10) NEED LADDER |
|
| 09/01/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO FURNACE VENT WEATHER CAP 2) DOUBLE LUGGING OF CIRCUIT BREAKERS NOT ALLOWED 3) LABEL ALL CIRCUITS IN ELECTRIC PANEL 4) SECURE ELECTRIC PANEL DEAD FRONT WITH TWO PROPER SCREENS 5) TIGHTEN AC WEATHER TIGHT NUTS AND SEURE WHIP WITHIN 12" OF DISCONNECT 6) SEAL OUTSIDE GFCI OUTLET AT WALL AND MISSING COVER 7) NO ACCESS TO PORCH GFCI . WET CONCRETE 8) ALL GARAGE CONVEAIELLE? OUTLETS MUST BE GFCI PROTECTED 9) NO FURNACE SPARK SHIELD 10) NO ATTIC LIGHT 11) NO ISLAND GFCI OUTLET 12) KITCHEN GFCI HOT WHEN TRIPPED 13) SOME KITCHEN OUTLET NO POWER 14) M. BATH HAS OPEN GROUND 15) PLUMBING NOT COMPLETE |