Permit: T05CM01256

Parcel: 140383460

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/06/2005 BUILDING - FINAL Approved IVRS - Inspection :*
09/01/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO FURNACE VENT WEATHER CAP
2) PROVIDE POST TENSION TAP AT WATER SVC
3) NO GAS BOND
4) DOUBLE LUGGING OF CIRCUIT BREAKERS NOT ALLOWED
5) MIXING ID GAGE AND 12 GAGE WIRES IN SAME CIRCUIT NOT ALLOWED
6) ACCESS TO A/C DISCONNECT BLOCKED BY CONDENSOR
7) NO ACCESS TO OUTSIDE GFCI OUTLET WET CONCRETE
STOPPED INSP TOO MANY ITEMS DID NOT GO INSIDE