Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/13/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/12/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 1, 5, 6 AND 7 NOT DONE |
|
| 07/07/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NO GAS TEST 2) LAVE DIRTY ARM CANNOT EXCEWED 1 1/2" 3) NO DWV TEST 4) DWV DRAIN MUST HAVE 1/4"-FT PITCH 5) PEX MUST BE 12" FROM CAN LIGHTS 6) MASTER W/C LESS THAN 15" TO WALL 7) NAIL PROTECT WIRES PATIO DOOR |