Permit: T05CM01248

Parcel: 116277600


Addresses:

3232 W TUMAMOC DR


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM01248

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2006 BUILDING - FINAL Approved IVRS - Inspection :*
07/13/2006 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) NEED CERTS
06/21/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE GRADING TO SLOPE AWAY FROM HOUSE
2) CUT SEWER CLEANOUTS TO GRADE
3) EXTERIOR DOOR MECH ROOM LOCKED
4) ITEM 03040 NEEDS TO BE EXPOSED FOR INSPECTION EACH END AND MIDWAY POINT
5) BEDROOM ARC FAULT BREAKERS INOPERATIVE
6) TUB WINDOW REQUIRES TEMPERED GLASS
7) ELECTRIC RECEPTACLES KITCHEN NOT TO PLAN
8) ELECTRIC AND GAS NOT PER PLAN
9) STOPPED INSPECTION