Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2005 | FRAMING | Approved | IVRS - Inspection :* OK TO INSULATE |
|
| 08/26/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) DOUBLE G3 SHEAR WALL REQUIRES STUDS AT 16" O.C 2) 12/SD4 NOT COMPLIED WITH 3) HOLD DOWNS NOT INSTALLED 4) G3 MISSING A 35 CLIPS 5) NO DWV WATER TEST 6) 10/SD4 NOT COMPLIED WITH 7) STOPPED INSP. HOUSE NOT COMPLETE |