Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM01240
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/12/2005 | FRAMING | Approved | IVRS - Inspection :* | |
08/11/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO TEST ON DWV SEE LAST INSP #2,4,6,7 AND 8 |
|
08/05/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEAL ALL LATH PENETRATIONS 2) ROMEX NOT TO BE STAPLED ON IT'S SIDE 3) NO TEST ON GAS LINE 4) NAIL PROTECT ELECTRIC WITHIN 1 1/4" FROM EDGE OF STUD 5) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR 6) NO TEST ON DWV'S 7) PROVIDE 1" CLEARANCE AT B-VENT FIREPLACE 8) FIRE BLOCKS MISSING AT FIRE PLACE |
|
08/01/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST TENSION CABLES NOT TENSIONED |
|
07/28/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. POST TENSION CABLES NOT TENSIONED |