Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/10/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/09/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REPAIR TO CONDENSATE MADE WITH AN APPARENT MODIFIED LISTED FITTING WHICH IS NOT APPROVED. PROVIDE A LIKE UNUSED COUPLING AND THE UPC LISTING FOR THAT PART |
|
| 08/08/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) HOLE IN CONDENSATE LINE-UP STAIRS |
|
| 08/04/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* HOLE IN CONDENSATE LINE M/BR FIRE STOP BR2 OK TO INSULATE |
|
| 08/01/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) LATH MISSING WIRE AT FRONT 2) W/H T & P LINE MUST EXHAUST 6" ABOVE SIDE WALK 3) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACE 4) HTT16 HOLDOWN NOT INSTALLED GARAGE P-3 SHEARWALL 5) ANCHOR BOLTS SPACING NOT PER PLAN ON SHEARWALLS 6) SUPPORT HORIZONTAL DWV WAT 4' ON CENTER WITH APPROVED SUPPORT 7) 1" CLEARANCE REQUIRED BETWEEN WATER HEATER B VENT AND ABS PLUMBING 8) TIMBER STRAND HANGER BY POWDER ROOM BENT TO LOOK LIKE SUPPORT. REPLACE HANGER 9) STOPPED INSPECTION-TO MANY ITEMS 10) SUPERINTENDENT TO INSURE HOUSE IS COMPLETE TO CODE AND PLAN PRIOR TO NEXT INSPECTION |