Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM01232
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) ITEM 03050 NOT APPLICABLE-NO GAS PER PAPERWORK TURNED IN BY INSPECTOR D. QUINN |
|
| 09/27/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #2 NOT DONE FROM INSPECTION DONE ON 9/23/05 |
|
| 09/23/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED LADDER FOR ATTIC ACCESS 2) NEED OUTLET NORTH OF COOK TOP 3) NEED SHOWER GLASS |
|
| 09/21/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO UFER IN PANEL 2) MOST WIRES BADLY NICKED AT INSULATION STRIP POINT. ED-DO PANEL AND CHECK EVERY FIXTURE IN HOUSE STOPPED INSPECTION - ELEC. SHUT OFF |
|
| 08/15/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* |