Permit: T05CM01218

Parcel: 115020240


Addresses:

309 E WAVERLY ST

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
03/23/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
03/13/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) MASONRY OVER EXISTING WINDOW EAST SIDE RAISED TO ACCOMODATE LARGER HEIGHT WINDOW
2) OK TO GROUT
03/08/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) STEM WALL OK TO GROUT
2) EXPOSE TIE-IN SEWER EAST SIDE OF STRUCTURE COVERED WITH DIRT
3) UNABLE TO FIND SEWER, SOIL PIPE ON PLANS
4) MUST HAVE 10' HEAD WALL WATER TEST ON PLUMBING
5) MUST COMPLETE ALL TRADES THEN CALL IN FOR ALL INTERMEDIATE INSPECTIONS
03/03/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) PREGROUT OK ON NORTH BATH WALLS
2) BOND BEAM OK
03/02/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*