Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/22/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LSL NOT NAILED PER PLAN 2) WEST P-1 SHEARWALL REQUIRES ANCHOR BOLTS AT 16" ON CENTER 3) OK TO INSULATE |
|
| 07/15/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) LATH REINFORCING NOT INSTALLED-NOT CAULKED 2) NO DWV WATER TEST 3) LSL NOT NAILED PER PLAN 4) 1" CLEARANCE REQUIRED W/H VENT TO WOOD 5) NO GAS TEST 6) FLOOR TRUSS CUT BY PLUMBING TWO PLACES PROVIDE CLEANOUT AND ENGINEERS APPROVED REPAIR 7) 2ND FLOOR SILL PLATES NOT NAILED TO FLOOR PER PLAN 8) EXHAUST FAN MUST EXHAUST OUTSIDE 9) 1/2" CLEARANCE REQUIRED BETWEEN LIGHT AND WOOD 10) LAUNDRY BIBS LOOSE 11) NAIL PROTECT PLUMBING WITHIN 1 1/4" OF STUD SURFACE 12) STOPPED INSPECTION TO MANY ITEMS 13) CHECK A.B. SPACING |