Permit: T05CM01204

Parcel: 141175170

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
05/31/2005 FRAMING Approved IVRS - Inspection :*
05/24/2005 FRAMING Partial Approval IVRS - Inspection :*
1) OK TO NET WALLS (EXT)-PLAN PROBLEMS TO RESOLVE
2) DWV NOT TESTED
3) GAS/H20 OK
05/23/2005 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO GAS PRESSURE TEST
2) 4/SD2 TRUSS BLOCKING NOT INSTALLED-MUST BE NAILED THRU ROOF
3) NO DWV WATER TEST
4) A/C CONDENSATE NOT COMPLETE
5) BEARING AND SHEARWALL STUDS CANNOT BE NOTCHED GREATER THAN 25 PERCENT
6) INSTALLED TRUSSES ARE NOT CORRECT TRUSSES
7) PLUMBING LEAKS
8) STOPPED INSPECTION