Permit: T05CM01197

Parcel: 13323111Q


Addresses:

7727 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/07/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/07/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) SUPPORT CONDUIT AS PER 300.11
2) CONDUCTOR OVER FILL
3) FINISH #1 PREVIOUS INSPECTION
08/19/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TIGHTEN LOOSE FITTINGS
2) PROTECT M/C CABLE IN CHANEL AND SUPPORT WITHIN 12" OF BOX
3) SUPPORT CONDUIT AS PER CODE A-D FLEX
4) OPEN DRYWALL AS DISCUSSED TO INSPECT
5) FILL UNUSED OPENINGS IN JUNCTION BOXES
6) AREA IS OCCUPIED AND USING ELECTRIC OUTLETS THAT ARE UN-SAFE
7) DO NOT OCCUPY UNTIL AREAS HAS PASSED INSPECTION BY ELECTRICAL AND BLDG INSPECTORS. THIS AREA IS UN-SAFE UNTIL INSPECTORS APPROVE