Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05CM01185

Parcel: 13311008A


Addresses:

7151 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T05CM01185

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2006 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
12/13/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
12/09/2005 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) OK SEC 1-1 MPDA, HVAC1, HVAC2, LPA, LPB, BROWN BOX (LIGHTING), CP1, RP1, TRANSFORMER PP1, TRANFORMER BW, BW AND CONTACTORS, BC, MDPB, TRANSFER SWITCH LIGHTING, TRANSFER SWITCH EM ?, BLS
2) LABEL TRANSFORMERS
3) FILL UNUSED OPEN MDPB
-------------------------------------------------------------------------------------------------12/10/05 RECEIVED CHECK #14259 FOR AFTER HOUR INSPECTION $108.00
OK CP2, SLA, SLB, TRANSFORMER RP2
OK BONDING OF OTHER METAL PIPING
408.3 (A)(3) CONDUCTORS TO BE ISOLATED THRU SECTION
LABEL MANUAL TRANSFER SWITCH AND DISCONNECTS
BOND CABLE TRAY