Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T05CM01185
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2006 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 12/13/2005 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* | |
| 12/09/2005 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) OK SEC 1-1 MPDA, HVAC1, HVAC2, LPA, LPB, BROWN BOX (LIGHTING), CP1, RP1, TRANSFORMER PP1, TRANFORMER BW, BW AND CONTACTORS, BC, MDPB, TRANSFER SWITCH LIGHTING, TRANSFER SWITCH EM ?, BLS 2) LABEL TRANSFORMERS 3) FILL UNUSED OPEN MDPB -------------------------------------------------------------------------------------------------12/10/05 RECEIVED CHECK #14259 FOR AFTER HOUR INSPECTION $108.00 OK CP2, SLA, SLB, TRANSFORMER RP2 OK BONDING OF OTHER METAL PIPING 408.3 (A)(3) CONDUCTORS TO BE ISOLATED THRU SECTION LABEL MANUAL TRANSFER SWITCH AND DISCONNECTS BOND CABLE TRAY |