Permit: T05CM01185

Parcel: 13311008A


Addresses:

7151 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Permit Number - T05CM01185

Inspection Description - ELECTRIC - CONSTRUCTION POWER

Inspection Status - Approved

Date Description Inspector Results Comments
01/18/2006 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
10/07/2005 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*OK SUBPANEL AT BUILDING (TEMP)
10/06/2005 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
1) INSTALL GROUNDING ELECTRODE SYSTEM AT BUILDING SUB-PANEL
09/02/2005 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
1) OK TO CLEAR CONSTRUCTION POWER
2) CALL FOR INSPECTION TO ENGERGIZE PANEL AT MAIN BUILDING
09/01/2005 ELECTRIC - CONSTRUCTION POWER Partial Approval IVRS - Inspection :*
1) WHERE IS 2ND GROUND ROD ? TRAILER CONNECT GROUND
2) CONDUIT RUNNING NORTH FROM SERVICE COVERED WITHOUT INSPECTIONS
30 FUSING TO BE EQUAL IN AMPACITY
08/30/2005 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
1) GROUNDING ELECTRODE SYSTEM NEEDED AT TRAILER
2) GROUND RODS WITH 8' OF SOIL CONTACT 6' APART AT SERVICE
3) ONLY ONE CONDUCTOR TO A LUG
4) SPLIT BOLT LISTED FOR ONLY RUN AND TAP
5) BOND JUMPER TO BE SIZED PER 250.102 AND 250.66 LINE SIDE
6) FILL UN-USED OPENINGS
7) A SPECIAL DEVICE IS NEEDED ABOVE CURRENT CARRING PARTS
08/23/2005 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY JERRY