Permit: T05CM01185

Parcel: 13311008A


Addresses:

7151 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM01185

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/29/2005 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/16/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) PROTECT CONDUCTOR FROM SHARP METAL EDGES OF SEAL TITE
2) OK HIGH BAY FIXTURES COVERED AREA GARDEN CENTER
3) OK HIGH BAY FIXTURES DRIVE THRU-LUMBER YARD VESTABULE
4) OK 4 POLES AT GARDEN CENTER
12/15/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*FRONT END:
1) VDV CABLEING NOT DONE AS #1 ON 12/12/05
GARDEN CENTER: DRIVE THRU
1) BOND JUNCTION BOX AT HIGH BAY LIGHTS 250.148
2) SECURE: OTHER END OF SAFETY CHAIN
3) INSTALL FLOOD LIGHTS ( 120V)
OK 120V ELECTRIC FRONT END.
12/12/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
12/08/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. BONDING JUMPER TO BE SIZED PER 250.102 & 250.66
2. FITTING TO BE APPROVED FOR BONDING GROUNDING ELECTRODE FROM TRANSFORMER.
3. SEAL UNUSED OPENING IN BOTTOM OF SWITCHBOARD
RECEIVED PAPERWORK FOR TORQUE AND GFI TESTING.
12/06/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK SOUTH OFFICES & RESTROOMS EXCEPT AT DOOR OPENERS
12/02/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK PVC CONDUIT AS MARKED
OK COLUMN (E) THRU (H) MAIN FLOOR.
12/3/05 OK PVC CONDUITS AS MARKED
OK 4 POLE BASES AS MARKED
RECEV CHECK # 01724553 FOR $ 108.00 AFTER HOURS
12/01/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*OK PARKING LOT AS MARKED ON PLANS PVC
OK SOUTH EAST END TO COLUMN (H) ON CEILING
11/30/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/16/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*M/C CABLE TO BE SUPPORTED WITHIN 12" OF BOX