Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM01185
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/16/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROTECT CONDUCTOR FROM SHARP METAL EDGES OF SEAL TITE 2) OK HIGH BAY FIXTURES COVERED AREA GARDEN CENTER 3) OK HIGH BAY FIXTURES DRIVE THRU-LUMBER YARD VESTABULE 4) OK 4 POLES AT GARDEN CENTER |
|
| 12/15/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*FRONT END: 1) VDV CABLEING NOT DONE AS #1 ON 12/12/05 GARDEN CENTER: DRIVE THRU 1) BOND JUNCTION BOX AT HIGH BAY LIGHTS 250.148 2) SECURE: OTHER END OF SAFETY CHAIN 3) INSTALL FLOOD LIGHTS ( 120V) OK 120V ELECTRIC FRONT END. |
|
| 12/12/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 12/08/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. BONDING JUMPER TO BE SIZED PER 250.102 & 250.66 2. FITTING TO BE APPROVED FOR BONDING GROUNDING ELECTRODE FROM TRANSFORMER. 3. SEAL UNUSED OPENING IN BOTTOM OF SWITCHBOARD RECEIVED PAPERWORK FOR TORQUE AND GFI TESTING. |
|
| 12/06/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK SOUTH OFFICES & RESTROOMS EXCEPT AT DOOR OPENERS | |
| 12/02/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK PVC CONDUIT AS MARKED OK COLUMN (E) THRU (H) MAIN FLOOR. 12/3/05 OK PVC CONDUITS AS MARKED OK 4 POLE BASES AS MARKED RECEV CHECK # 01724553 FOR $ 108.00 AFTER HOURS |
|
| 12/01/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*OK PARKING LOT AS MARKED ON PLANS PVC OK SOUTH EAST END TO COLUMN (H) ON CEILING |
|
| 11/30/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/16/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*M/C CABLE TO BE SUPPORTED WITHIN 12" OF BOX |