Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM01160
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
12/12/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PROVIDE DUCT SMOKE DETECTOR -- OK TEMP C OF O |
|
11/22/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*PROVIDE A FULL SIZE DRAIN PAN AS PER CODE. PROVIDE A TRAP ON CONDENSATE DRAIN LINE. CONNECT OVERFLOW SENSOR ON PUMP. PROVIDE AN ELECTRICAL CIRCUIT FOR FAN COIL. YOU CANNOT USE A PLUG IN CORD ABOVE A CEILING. INSTALL E 2 TRAP. OK TO INSULATE WATER LINES. PROVIDE DUCT SMOKE DETECTOR. |
|
11/15/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*SECONDARY CONDENSATE PAN MUST COVER THE ENTIRE UNIT 1 1/2" LARGER ON ALL SIDES OF FAN COIL. PROVIDE A TRAP ON CONDENSATE DRAIN LINE. CONNECT OVERFLOW SENSOR ON PUMP. FINISH WATER PIPING. PRESSURE TEST NOT HOLDING ON WATER PIPING |