Permit: T05CM01160

Parcel: 12701005D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/17/2006 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/12/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
PROVIDE DUCT SMOKE DETECTOR -- OK TEMP C OF O
11/22/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*PROVIDE A FULL SIZE DRAIN PAN AS PER CODE. PROVIDE A TRAP ON CONDENSATE DRAIN LINE. CONNECT OVERFLOW SENSOR ON PUMP. PROVIDE AN ELECTRICAL CIRCUIT FOR FAN COIL. YOU CANNOT USE A PLUG IN CORD ABOVE A CEILING. INSTALL E 2 TRAP.
OK TO INSULATE WATER LINES. PROVIDE DUCT SMOKE DETECTOR.
11/15/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*SECONDARY CONDENSATE PAN MUST COVER THE ENTIRE UNIT 1 1/2" LARGER ON ALL SIDES OF FAN COIL.
PROVIDE A TRAP ON CONDENSATE DRAIN LINE. CONNECT OVERFLOW SENSOR ON PUMP. FINISH WATER PIPING. PRESSURE TEST NOT HOLDING ON WATER PIPING