Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM01160
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/18/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL 1. RAUL TO FIX KIOSK DOORS |
|
04/12/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WE STILL HAVE A WALL ASSEMBLY NOT A CABINET AS DISCUSSED FOR KIOSK. 2. USE APPROVED FITTING FOR M/C CABLE 3. GROUND JUNCTION BOXES 4. STRAP AND SUPPORT M/C CABLE 5. USE PROPER SIZED STRAPS FOR M/C CABLE. 6. BUILDING INSPECTOR TO CHECK FIRE STOPPING OK PLANTER AND RECEPTION COUNTER. |
|
04/05/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
04/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT M/C CABLE AND SPLICES TO BE MADE IN JUNCTION BOXES ALSO CORDS ABOVE CEILING -- SUNSCREENS PLEASE PROVIDE INSTRUCTIONS. 2. FINISH PREVIOUS ITEMS 2, 3 & 6 |
|
03/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) INTERMATIC TIMER/TRANSFORMER FOR OUTDOORS ONLY 2) CORDS NOT TO BE IN ? SPACES 400.7 + 8 3) PLEASE VERIFY LISTING FOR TIGER CONTROLLER 4) PLEASE PROVIDE ACCESS TO SUN SCREENS TO INSPECT CONNECTIONS AND LISTINGS 5) FAN COIL DISCONNECT NOT ACCESSIBLE 6) SEAL BOTTOM OF FIRE PENETRATIONS 7) PLANS CALL FOR CIRCUITS TO "EDP" BUT PANEL SCHEDULE DOES NOT REFLECT CIRCUITS OR LOADS. HOW CAN A NEW PANEL HAVE EXISTING LOADS 8) PLEAS HAVE ELECTRICIAN PRESENT TO OPEN UP PANELS FOR INSPECTION 9) AREA OCCUPIED WITHOUT FINAL INSPECTIONS |
|
03/03/2006 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |