Permit: T05CM01160

Parcel: 12701005D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM01160

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/18/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
1. RAUL TO FIX KIOSK DOORS
04/12/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WE STILL HAVE A WALL ASSEMBLY NOT A CABINET AS DISCUSSED FOR KIOSK.
2. USE APPROVED FITTING FOR M/C CABLE
3. GROUND JUNCTION BOXES
4. STRAP AND SUPPORT M/C CABLE
5. USE PROPER SIZED STRAPS FOR M/C CABLE.
6. BUILDING INSPECTOR TO CHECK FIRE STOPPING
OK PLANTER AND RECEPTION COUNTER.
04/05/2006 ELECTRIC - FINAL Cancelled IVRS - RI canceled
04/05/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SUPPORT M/C CABLE AND SPLICES TO BE MADE IN JUNCTION BOXES ALSO CORDS ABOVE CEILING -- SUNSCREENS PLEASE PROVIDE INSTRUCTIONS.
2. FINISH PREVIOUS ITEMS 2, 3 & 6
03/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) INTERMATIC TIMER/TRANSFORMER FOR OUTDOORS ONLY
2) CORDS NOT TO BE IN ? SPACES 400.7 + 8
3) PLEASE VERIFY LISTING FOR TIGER CONTROLLER
4) PLEASE PROVIDE ACCESS TO SUN SCREENS TO INSPECT CONNECTIONS AND LISTINGS
5) FAN COIL DISCONNECT NOT ACCESSIBLE
6) SEAL BOTTOM OF FIRE PENETRATIONS
7) PLANS CALL FOR CIRCUITS TO "EDP" BUT PANEL SCHEDULE DOES NOT REFLECT CIRCUITS OR LOADS. HOW CAN A NEW PANEL HAVE EXISTING LOADS
8) PLEAS HAVE ELECTRICIAN PRESENT TO OPEN UP PANELS FOR INSPECTION
9) AREA OCCUPIED WITHOUT FINAL INSPECTIONS
03/03/2006 ELECTRIC - FINAL Cancelled IVRS - RI canceled