Permit: T05CM01144

Parcel: 10604098C

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
05/23/2007 FIRE - FINAL Approved
05/08/2007 FIRE - FINAL Denied 1. IFC APPENDIX "D" : FIRE LANE SIGNS SHALL BE OF APPROVED TYPE. POSTING OF SIGNS SHALL BE IN THE DIRECTION OF TRAVEL AND NOT LESS THEN 7 FEET OR MORE THAN 10 FEET FROM GROUND SURFACE LEVEL TO BOTTOM OF SIGN.

2. IFC 907.2.10.2 POWER SOURCE: SMOKE ALARMS SHALL HAVE BATTERY BACK UP AND BE HARD WIRED. INSTALL BATTERY BACK UP AND HARD WIRE TYPE SMOKE ALARMS.
04/30/2007 FIRE - FINAL Denied Need to post Fire lane signs per plans on SD1.
Need to operate all security bars on windows need a person on site to do this.
03/23/2007 FIRE - FINAL Denied NEED TO HAVE FIRE SPRINKLER CONTRACTOR ON SITE TO DO FINAL ALARM TEST AND FLOW TEST FOR SPRINKLER SYSTEM, HAVE SPRINKLER CONTRACTOR CALL IN THERE PERMIT.
NEED TO HAVE UNIT NUMBER ON ALL UNITS FOR ADDRESSING