Permit: T05CM01144

Parcel: 10604098C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/08/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. UNIT #3 ANTI-TIP ON RANGE STILL NOT WORKING
2. SEAL OPENINGS IN HOUSE PANEL WITH K.O SEAL
NOT DUCT TAPE ALSO, NEED INDIVIDUAL NEUTRALS TO NEUTRAL BAR FOR PANEL RECEPTACLES.
3. UNIT #1 STORAGE STILL LOCKED - REFEE IF NOT CORRECT NEXT TRIP
04/30/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
HOUSE SUB-PANEL
1. SEAL UNUSED OPENINGS
2. 3-WIRE HOMERUNS TO TERMINATE ON OPPOSITE PHASES
3. HAVE STORAGE UNITS UNLOCKED
4. PROVIDE ROOF ACCESS

UNIT #1 - WHERE IS AC CKT IN PANEL?
UNIT #2 - EAST BEDROOM SMOKE DETECTOR NOT INTERCONNECTED, WHERE IS AC CKT? TIGHTEN LOOSE RECEPTACLES
UNIT #3 - RANGE ANTI-TIP DEVICE NOT WORKING WHERE IS A.C IN PANEL KITCHEN SINK LIGHT NOT WORKING.

NOTE: IDENTIFY AC'S IN PANELS -- NO DRYERS
03/23/2007 ELECTRIC - FINAL Not ready for Inspection CALL FOR FINAL AFTER POWER IS TURNED ON