Permit: T05CM01144

Parcel: 10604098C

Inspection Status: Approved

Inspection History: SHEET ROCK NAILING

Date Description Inspector Results Comments
09/27/2006 SHEET ROCK NAILING Approved IVRS - Inspection :*
09/25/2006 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*
UNITS 2, 3 ONLY
09/21/2006 SHEET ROCK NAILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RATED AREA SEPARATION WALLS (FIRE BARRIERS) NEED TO BE TIGHT CONSTRUCTION - 1/8" GAP MAXIMUM.
- FILL GAPS WITH INTUMESCENT OR FIRE MUD & RECALL.
2. YOU MAY NOT USE PLASTER RINGS IN RATED WALLS. REPLACE RINGS WITH LISTED BOXES.
3. YOU MAY NOT USE PLASTIC FRIDGE BOXES IN RATED WALLS.
08/16/2006 SHEET ROCK NAILING Partial Approval IVRS - Inspection :*