Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM01139
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2005 | ELECTRIC - ABOVE CEILING | Approved | ||
04/13/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
04/04/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) #4 OF PREVIOUS IS FOR THER? STATE AND FIRE ALARM CABLES. 2) PLEASE INSTALL A JUNCTION BOX ON EXPOSED SIGN CONDUCTORS. OK 2 X4 LIGHTS OK TO TILE EXCEPT AS NOTED. | |
03/31/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PLEASE SUPPORT FIXTURE WHIPS UP OFF OF CEILING TILES. 2) FIXTURES TO BE SECURLY ATTACHED TO GRID. IF 2 SCREWS ARE USED THEY MUST BE IN CENTER. IF ATTACHMENT IS IN CORNERS 4 SCREWS MUST BE USED. 3) ELECTRIC NOT TO BE SUPPORTED OFF OF CEILING SUPPORT WIRES. IT IS TO BE INDEPENDENTLY SUPPORTED 300.11 4) SUPPORT VDV CABLES AS PER 725.2. 5) WHAT ARE EXPOSED CONDUCTOR ON FRONT WALL? 6) A SUPPORT WIRE IS NEEDED FRO EXIT LIGHTING |