Permit: T05CM01137

Parcel: 121092890

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05CM01137

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/15/2006 MECHANICAL - FINAL Approved
06/05/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
06/02/2006 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GREASE DUCT WELDS NOT INSPECTED. REMOVE FIRE WRAP.
TYPE I HOOD MUST HAVE MIN. 18" CLEARANCE FROM ALL WOOD FRAMED CONSTRUCTION. THIS INCLUDES THE TOP OF THE HOOD & SIDE WALL.
PROVIDE A DUCT SMOKE DETECTOR IN FURNACE RETURN DUCT W/AUDIBLE & VISIBLE ALARMS.
PROVIDE INSTALL INSTRUCTIONS FOR FURNACE.
PROVIDE A GUARD RAIL @ EVAP. COOLER AS PER IMC.
MECH. CONTRACTOR MUST BE ON SITE FOR NEXT INSPECTION.
05/30/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. NO HISTORY OF EXH. DUCT WELD INSPECTION, RIGID CHASE OR FIRE WRAP INSPECTION, ETC.
2. COMBUSTIBLES AT REAR OF AND POSSIBLE LEFT SIDE OF TYPE 1 HOOD. SEE SEC. 605.36 FOR NON-COMBUSTIBLES AT REAR OF HOOD.
3. NO APPROVED INTERMEDIATE INSPECTIONS.