Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05CM01137
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2006 | MECHANICAL - FINAL | Approved | ||
| 06/05/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/02/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GREASE DUCT WELDS NOT INSPECTED. REMOVE FIRE WRAP. TYPE I HOOD MUST HAVE MIN. 18" CLEARANCE FROM ALL WOOD FRAMED CONSTRUCTION. THIS INCLUDES THE TOP OF THE HOOD & SIDE WALL. PROVIDE A DUCT SMOKE DETECTOR IN FURNACE RETURN DUCT W/AUDIBLE & VISIBLE ALARMS. PROVIDE INSTALL INSTRUCTIONS FOR FURNACE. PROVIDE A GUARD RAIL @ EVAP. COOLER AS PER IMC. MECH. CONTRACTOR MUST BE ON SITE FOR NEXT INSPECTION. |
|
| 05/30/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. NO HISTORY OF EXH. DUCT WELD INSPECTION, RIGID CHASE OR FIRE WRAP INSPECTION, ETC. 2. COMBUSTIBLES AT REAR OF AND POSSIBLE LEFT SIDE OF TYPE 1 HOOD. SEE SEC. 605.36 FOR NON-COMBUSTIBLES AT REAR OF HOOD. 3. NO APPROVED INTERMEDIATE INSPECTIONS. |