Permit: T05CM01137

Parcel: 121092890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM01137

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/01/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
05/30/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. FILL UNUSED OPENINGS IN CEILING FIXTURES.
2. RECEPTACLE BEHIND STOVE TO BE GFCI 210.8
3. TIGHTEN LOOSE SET SCREW FITTINGS.
4. ARE EXISTING CONDUCTORS IN BOXES BEHIND SURFACE BOXES LIVE? IF SO PLEASE CAP OFF.
5. SUPPORT VDV CABLING AS PER 725.6 & VERIFY IF PLENIUM RATED.
6. IF USING MANUFACTURERS CLIPS THEY MUST BE EFFECTIVE
7. PLEASE PROVIDE CIRCUIT DIRECTORY FOR PANEL.
8. NEED ELECTRICIAN TO OPEN PANEL FOR INSPECTION.
9. WE HAVE BOX OVERFILL IN ATTIC - 2 BOXES
10. ONLY ONE CONDUCTOR TO LUG TERMINATION.
11. DRYWALL SCREW NOT ALLOWED FOR GROUNDING
12. HOS IS INTERLOCK WORKING.