Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM01137
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/01/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL |
|
| 05/30/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FILL UNUSED OPENINGS IN CEILING FIXTURES. 2. RECEPTACLE BEHIND STOVE TO BE GFCI 210.8 3. TIGHTEN LOOSE SET SCREW FITTINGS. 4. ARE EXISTING CONDUCTORS IN BOXES BEHIND SURFACE BOXES LIVE? IF SO PLEASE CAP OFF. 5. SUPPORT VDV CABLING AS PER 725.6 & VERIFY IF PLENIUM RATED. 6. IF USING MANUFACTURERS CLIPS THEY MUST BE EFFECTIVE 7. PLEASE PROVIDE CIRCUIT DIRECTORY FOR PANEL. 8. NEED ELECTRICIAN TO OPEN PANEL FOR INSPECTION. 9. WE HAVE BOX OVERFILL IN ATTIC - 2 BOXES 10. ONLY ONE CONDUCTOR TO LUG TERMINATION. 11. DRYWALL SCREW NOT ALLOWED FOR GROUNDING 12. HOS IS INTERLOCK WORKING. |