Permit: T05CM01128

Parcel: 11005314D


Addresses:

3175 N SWAN RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/08/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/27/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) UNDERGROUND PIPING FOR OUTDOOR MOP SINK IS OK
2) INSTALL FCO
05/25/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PRESSURE TEST ACCEPTED - YARD WATER LINE.
REMOVE ALL ROCKS FROM PIPING INCLUDING SECTION THAT HAS ALREADY BEEN COVERED.
PROVIDE SUPPORT UNDER PIPING.
05/23/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1 1/2" NOT UNDER TEST.
2 1/2" HS 60 PSI AIR TEST.
DO NOT TEST PVC W/AIR!
THIS IS A SAFETY HAZARD AND AN OSHA VIOLATION.
05/18/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOT HOLDING TEST.
HYDRO TEST REQUIRED ON PLASTIC PIPE.