Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM01128
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
06/27/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) UNDERGROUND PIPING FOR OUTDOOR MOP SINK IS OK 2) INSTALL FCO |
|
05/25/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PRESSURE TEST ACCEPTED - YARD WATER LINE. REMOVE ALL ROCKS FROM PIPING INCLUDING SECTION THAT HAS ALREADY BEEN COVERED. PROVIDE SUPPORT UNDER PIPING. |
|
05/23/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1 1/2" NOT UNDER TEST. 2 1/2" HS 60 PSI AIR TEST. DO NOT TEST PVC W/AIR! THIS IS A SAFETY HAZARD AND AN OSHA VIOLATION. |
|
05/18/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOT HOLDING TEST. HYDRO TEST REQUIRED ON PLASTIC PIPE. |