Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM01118
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2005 | FRAMING | Approved | IVRS - Inspection :* | |
05/24/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) BANG PLATE ROMEX EAST GARAGE, EAST WALL LIVING ROOM 2) WYE FITTING TO BE POLLED UP ABOVE CENTER LINE FLAT VENT NEED POSITIVE PITCH 3) NEED A HANG CHANGED THA 422 DON'T WORK AT BEAM STRAPS TO LONG 302/S-3 4) BACKING CUT LIV, MSTR. BED DOOR OPENING 5) DIVERTER STUD CUT MASTER SHOWER 6) FIX HOLE IN 2ND FLOOR, AT TOP OF STAIR (DECK) 7) DIVERTER IN BEHIND DRYER DUCT 8) BLOCK FLOOR AT JOINT 2ND FLOOR WEST WALL 9) FINISH LATH 10) DBL STUD AT EAST KITCHEN WALL SHEAR CUT 11) A.B. AT 32" ON CENTER #4 SHEARWALL INTERIOR 12) TO MUCH SHEET ROCK STACKED IMPROPERLY 13) GAS/H20/DWV-OK |