Permit: T05CM01094

Parcel: 121061360


Addresses:

5838 E CAMDEN ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/02/2005 BUILDING - FINAL Approved IVRS - Inspection :*
10/31/2005 BUILDING - FINAL Partial Approval IVRS - Inspection :*
NEED STUCCO AND INSULATION CERTIFICATES
10/17/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MARK PANEL FOR MAIN BREAKER, UNUSED BREAKER, NO WATER BOND
2) SEAL STUCCO AT TPR DRAIN AND SHEETROCK
3) RAISE DISHWASHER DRAIN LINE TO BOTTOM OF COUNTER TOP
4) CLAMP OPEN FIRE PLACE DAMPER
5) MISSING COVER PLATE AT KITCHEN AND SINK
6) TAPE H20 HEATER FLUE JOINTS
7) A/C IS PRESENTLY OVERFUSED WITH 60 AMP BREAKERS-NEEDS 50 MAXIMUM
8) ROOF MOUNTED OUTLET, FOR A/C MAINTENANCE, HAS NO COVER
9) CONDUIT FOR PENETRATES ROOF WITH NO APPROPRIATE ROOF PENETRATION JACK
PRESENTLY RELIES ON TAR
10) PATCH ROOF COATING AROUND A/C UNIT