Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/31/2005 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* NEED STUCCO AND INSULATION CERTIFICATES |
|
| 10/17/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MARK PANEL FOR MAIN BREAKER, UNUSED BREAKER, NO WATER BOND 2) SEAL STUCCO AT TPR DRAIN AND SHEETROCK 3) RAISE DISHWASHER DRAIN LINE TO BOTTOM OF COUNTER TOP 4) CLAMP OPEN FIRE PLACE DAMPER 5) MISSING COVER PLATE AT KITCHEN AND SINK 6) TAPE H20 HEATER FLUE JOINTS 7) A/C IS PRESENTLY OVERFUSED WITH 60 AMP BREAKERS-NEEDS 50 MAXIMUM 8) ROOF MOUNTED OUTLET, FOR A/C MAINTENANCE, HAS NO COVER 9) CONDUIT FOR PENETRATES ROOF WITH NO APPROPRIATE ROOF PENETRATION JACK PRESENTLY RELIES ON TAR 10) PATCH ROOF COATING AROUND A/C UNIT |