Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/19/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/17/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINAL SUBJECT TO CITY APPROVED STAMP FOR REVISED ELECTRICAL | |
| 05/16/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*1) FINISH ITEMS # 1 &3 OF INSPECTION DATED 5/03/05 | |
| 05/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* |
|
| 05/03/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE SERVICES ARE LABELED BY # 7310, 7312,7314,7314 THE PLANS SHOW PANELS AS BEING A,B,C,D. THE PANELS ARE MARKED #1, 2,3,4. ALL THREE MARKING SHOUD COINCIDE. 2) PLAN SHOWS WATER HEATER DISCONNECT BY WATER HEATER THERE IS ONLY A J-BOX. 3) PLAN SHOW WATER HEATER CIRCUIT FEE TO GOT TO PANEL A 23,25 HOWEVER THE PANEL SCHEDULE ON A DOES NOT SHOW THIS? CORRECT AND RECALL. |
|
| 04/29/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |