Permit: T05CM01039

Parcel: 141017460


Addresses:

5896 S COURTLAND DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T05CM01039

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/11/2005 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
1) NEED AND ANSWER FOR USING OR NOT USEING DETAILS 301, 302, 325 AND 326 STRAPS OR NO STRAPS IN BETWEEN FLOOR
05/09/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) ITEM #2 SHEAR PANELS, #3 SHEAR GOES CONTINOUS THRU COL. FRONT ENTRY
2) BROKEN FLOOR TRUSS
3) GARAGE ROOF SEE O.S.B. NOT SECURED AT EXT. CORNER
4) REAR SHEAR BETWEEN FLOOR NOT TIED
5) FLOOR NOT NAILED
6) ATTACH TOP OF SHEAR PER DETAIL AT TRUSS CHORD
05/04/2005 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) MISSED NAILING ON GARAGE ROOF
2) MISSED 3 SHEAR PANELS
3) INSTALL RAT RUNS ON FT1 TRUSSES
4) CONNECT SHEAR 1ST TO 2ND FLOOR
5) NEED SHEAR TRANSFER 2ND FLOOR TO ROOF PER SCHEDULE LPT4'S (413)
6) BROKEN FLOOR TRUSS
7) TIE GABLE END TRUSSES TO TOP PLATE 12" ON CENTER 16D'S
8) ALL BELLY BAY NAILING NOT COMPLETE
9) WRONG SIZED HEADER EAST WALL 2ND FLOOR 4'-0" WINDOW