Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/26/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/21/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ( EMERGENCY BACK UP LIGHTING) THE EXTENSION CORDS CANNOT PASS THROUGH SHEETROCK. NEED TO INSTALL RECEPTACLE AT EMERGENCY LIGHT LOCATION. 2) SMOKE DETECTORS NEED TO BE MIN. 3" AWAY. FROM AIR REGISTER & INTERLOCK WITH ALL OTHER SMOKE DETECTORS. 3) ELECTRICAL COVERED W/OUT INSPECTION FOR ELEC. RECEPTACLES & SMOKE DETECTORS & EMERG. LIGHTING REPAIR & RESCHEDULE INSP. 740-6970. WORK TO REFLECT APPROVED PLANS. |