Permit: T05CM01018

Parcel: 134071880


Addresses:

8509 E KENYON DR

Inspection Status: Not ready for Inspection

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/02/2005 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
09/02/2005 BUILDING - FINAL Approved IVRS - Inspection :*
05/25/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HOME HAS NOT BEEN MADE TO COMPLY WITH PREVIOUSLY NOTED VIOLATIONS
03/21/2005 BUILDING - FINAL Denied 1) HOME DOES NOT COMPLY WITH ACCESSIBLE EGRESS REQUIREMENTS E.G LEVER HARDWARE, EMERGENCY EXIT LIGHTING, THRESHOLD HEIGHTS ETC. 2) THE PLUMBING HAS BEEN MODIFIED TO INCLUDE NEW TOILETS AND SINKS THAT MUST BE INSPECTED AND APPROVED. 3) ELECTRICAL INSPECTIONS MUST BE PERFORMED AND APPROVED FOR LIGHTING AND INTERCONNECTED SMOKE DETECTORS. 4) OWNER CURRENTLY HAS A CERTIFICATE OF OCCUPANCY FOR 8 CLIENTS. HOME DOES NOT MEET CITY OF TUCSON STANDARDS FOR MORE THAN 5 CLIENTS. I AM GOING TO RECOMMEND THAT C OF O BE REVOKED AS BEIND ISSUED IN ERROR. ( C OF O ISSUED 5-02). 5) GAS PIPING DOES NOT MEET UPC STANDARDS. A HAZARD EXISTS IN MECHANICAL CLOSET. GAS PIPING NOT SUPPPORTED. SHUT OFFS TO EQUIPMENT MISSING. 6) DOUBLE KEYED DEAD BOLTS NOT ALLOWED ON EXIT DOORS. 7) YOUR PLAN WAS APPROVED IN ERROR. SECTION 1013.2 OF THE IBC DOES NOT ALLOW EGRESS THROUGH OTHER BEDROOMS OR BATH ROOMS.