Permit: T05CM01015

Parcel: 11517037A

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
12/21/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
08/21/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
TEP HAS NOT FINALED NEW PEDESTAL SITE, TRENCHING NOT DONE, CALL FOR CD ONCE TRENCHING DONE
03/27/2007 ELECTRIC - CABLE DROP Denied 1. SERVICE NEEDS TO BE ADDRESSED BY PERMANENT MEANS, NO MARKER - STREET ADDRESS & UNIT #'S
2. INSTALL A GROUND BUSHING WITH A #4 COPPER JUMPER TO FRAME LUG.
3. EITHER DEAD END ALL DEVICES INSIDE WITH WIRE NUTS OR TRIM.

CALL BACK WHEN 1-3 DONE SO POWER CAN BE RELEASED
CALL TO TEP THEY HAVE TO OK SERVICE
ALSO, THEY NEED YOUR TRENCH DONE.