Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/11/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL 600 AMP LPS-RK FUSES IN SERVICE DISCONNECT PER PLAN 2) SUPPORT MC CABLES ENTIRE RUNS FROM PANEL HF TO LOAD TERMINATION, CALL FOR INSPECTION WHEN READY, HAVE LADDER FOR INSPECTOR |