Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/20/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/15/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :ANSWERED QUESTIONS ABOUT REVISING OF PLANS. | |
| 11/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*PLANS SHOW CT EQUIPT ISNTALLED. IF NOT PLEASE PROVIDE LETTER STATING INTENT FROM ENGINEER | |
| 10/12/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK FOR TEMP C OF O WAITING ON PLANS REVISIONS | |
| 10/11/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* WE NOW HAVE WORKING & ?? SPACE CLEARANCE AT X -RAY DISCONNECT PLEASE LABEL X RAY DISCONNECT CORRECTLY WAITING ON PLAN REVISION FROM WILDAN FINISH #3 PREVIOUS ITEM |
|
| 10/10/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 10/03/2005 | ELECTRIC - FINAL | Partial Approval | FILL UNUSED OPENING IN X RAY DISCONNECT AND CORRECTLY LABEL INSTALL X RAY EQUIPMENT OR PROVIDE LETTER BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING RE LABEL WATER HEATER DISCONNECT LABEL PANELS O OUTSIDE COVERS FINISH VDV ROOM PLEASE HAVE REVISED PLANS ON SITE |