Permit: T05CM00979

Parcel: 122030820


Addresses:

2019 N BELL AV #02

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/13/2005 BUILDING - FINAL Approved IVRS - Inspection :*
05/06/2005 BUILDING - FINAL Partial Approval 1) ROOF CONSTRUCTION AT REAR PORCH, 2 X 4 RAFTERS 24" ON CENTER NOT PER CODE. HAVE DRAWING APPROVED
2) RELATE LAST INSPECTION TO PREVIOUS INSPECTOR
05/05/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO ANSWER AT FRONT DOOR
2) PLEASE RECALL
04/14/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) WATER HEATER WIRE SHALL BE PROTECTED
2) VACCUM BREAKERS AT HOSE BIBBS SHALL BE WITH PERMANENT SET SCREW
3) EXISITING ROOF AT REAR PORCH IS A HAZARD WILL NOT WITHSTAND A 20 LB LIVE LOAD PER ? FT.
03/11/2005 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFI IN KITCHEN DOES NOT TEST
2) PRESSURE RELIEF VALVE AT WATER HEATER MUST BE EXTENDED TO EXTERIOR 6"-24" ABOVE GROUND WITH 90 FITTING POINTING TOWARDS GROUND
3) SMOKE DETECTOR DOES NOT TEST. SMOKE DETECTOR NOT LABELED ON PLANS
4) INSTALL ANTI-SIPHON ON ALL HOSE BIBS
5) PAINT ROOF VENTS
6) MAIN SERVICE PANEL DBL LUGGED 15 AMP BREAKER. LABEL ALL CIRCUITS. NO SPLICES ALLOWED IN SERVICE TO HOT LEADS. ALL HOLT LEADS MUST BE RED OR BLACK
7) REVISE PLAN TO SHOW PATIO COVER
8) ALL ROMEX AT PATIO COVER UNDER 8' MUST BE PROPERLY COVERED
9) PROPER HARDWARE NEEDED AT ALL PATIO COVER CONNECTIONS