Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM00963
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/26/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/25/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/14/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* 1. I NEED PLANS ON SITE AND EQUIPMENT OPEN FOR INSPECTION (X-FORMER & PANELS). |
|
02/27/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*SERVICE BONDING HAS UNDER SIZED CONDUCTOR NEC 250.66 PROVIDE STRUCTURAL SPECIFICATIONS / PLAN REVIEW FOR TRANSFORMER INSTALLATION LOCATION ( NEW) A.C DISCONNECTS NEED TO BE ID AND BROUNDED PROPERLY, ALSO INSTALL FUSES AND STRAP FLEX USE BUSHING ON # 4 AND LARGER CONDUCTORS TRANSFORMER NOT BONDED/GROUNDED PER CODE NEC 250.30 TIGHTEN ALL GROUNDING BUSHING AND CONNECTIONS WILL FINISH INSEPCTION NEXT TRIP |
|
02/24/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |