Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM00953
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
06/24/2005 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SERVICE PANEL LABEL NOT H20 BONDED SYSTEM FINISH WIRING IRRIGATION SYSTEM 2) NO GAS BOND AT EXT. TERMINATION 3) DAMPER ON NORTH WALL WON'T OPEN 4) NO FUSES IN A/C DISCONNECT 5) STUCCO NOT SEALED AT PORCH 6) GALVANIZED TO CU. FITTING AT IRRIGATION 7) LIGHT MSTR CLOSET NEED 12" FROM SHELF |
|
06/14/2005 | BUILDING - FINAL | Cancelled | CANCELLED PER SUPER | |
06/13/2005 | BUILDING - FINAL | Cancelled | CANCELLED PER PAPERWORK TURNED IN BY INSPECTOR F. GREER |