Permit: T05CM00940

Parcel: 108240850


Addresses:

2494 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM00940

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) EARTH NOT TO SERVE AS SOLE GROUND FOR GUTTER NEC 250.4 (A) (5)
02/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. SERVICE CONDUCTORS ENTERING BUILDING ARE EXCESSIVE NEC 230
2. NEED TO CONTINUE INSPECTION WHEN I HAVE ACCESS TO ALL EQUIPMENT AND EQUIPMENT CAN BE DE-ENERGIZED
02/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED BUSHING FOR CONDUCTORS #4 AND LARGER
2. TRANSFORMER 4 NEEDS CONNECTION TO ELECTRODE AND TERMINATED UNDER SAME CONNECTION TO BONDING JUMPER AND NEED TO DO INSPECTION FOR DISCONNECT
3. CONTRACTOR WILL RESCHEDULE INSPECTION TO PROVIDE ACCESS TO ALL EQUIPMENT
02/06/2006 ELECTRIC - FINAL Cancelled CANCELLED PER CONTRACTOR DAN #275-0428
02/06/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/02/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
02/01/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
01/25/2006 ELECTRIC - FINAL Not ready for Inspection A NEW PERMIT MUST BE OBTAINED FOR THE MRI CENTER. THIS PERMIT AND ACTIVITY NUMBER WAS FOR THE BUILDING SHELL ONLY, AND HAS ALREADY BEEN FINALED.
01/20/2006 ELECTRIC - FINAL Cancelled IVRS - AP canceled
CANCELLED PER JOANN 1/20/06 @ 1 PM
10/06/2005 ELECTRIC - FINAL Partial Approval
10/06/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK FINAL
10/03/2005 ELECTRIC - FINAL Denied FINISH ?? BUTTON 7 TIE IN
EXTENDER RINGS ( TILE)
FINISH LOBBY CABINET & INSTALL RECEPTACLE
09/29/2005 ELECTRIC - FINAL Partial Approval BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
CANNOT SUPPORT OFF OF COPPER PIPES
FIXTURES TO BE ATTACHED TO GRID 410.16
BOND EXHAUST FAN ENCLOSURE. NOT UNDER A MOUNTING SCREW.
STRAP 2" FLEX CONDUIT
FILL UNUSED OPENINGS TOP PANEL "EP-2"
SUPPORT WIRES TO BE AS PER 300.11 ATTACHED BOTH ENDS
FINISH ELECTRIC.
IVRS - Inspection :*
09/18/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
08/26/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) DISCUSSED CLEARANCE ISSUE IN ELECTRIC EQUIPMENT ROOM AND RELOCATION OF EXISTING ELECTRIC EQUIPMENT