Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM00940
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) EARTH NOT TO SERVE AS SOLE GROUND FOR GUTTER NEC 250.4 (A) (5) |
|
| 02/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. SERVICE CONDUCTORS ENTERING BUILDING ARE EXCESSIVE NEC 230 2. NEED TO CONTINUE INSPECTION WHEN I HAVE ACCESS TO ALL EQUIPMENT AND EQUIPMENT CAN BE DE-ENERGIZED |
|
| 02/09/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED BUSHING FOR CONDUCTORS #4 AND LARGER 2. TRANSFORMER 4 NEEDS CONNECTION TO ELECTRODE AND TERMINATED UNDER SAME CONNECTION TO BONDING JUMPER AND NEED TO DO INSPECTION FOR DISCONNECT 3. CONTRACTOR WILL RESCHEDULE INSPECTION TO PROVIDE ACCESS TO ALL EQUIPMENT |
|
| 02/06/2006 | ELECTRIC - FINAL | Cancelled | CANCELLED PER CONTRACTOR DAN #275-0428 | |
| 02/06/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/02/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/01/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/25/2006 | ELECTRIC - FINAL | Not ready for Inspection | A NEW PERMIT MUST BE OBTAINED FOR THE MRI CENTER. THIS PERMIT AND ACTIVITY NUMBER WAS FOR THE BUILDING SHELL ONLY, AND HAS ALREADY BEEN FINALED. | |
| 01/20/2006 | ELECTRIC - FINAL | Cancelled | IVRS - AP canceled CANCELLED PER JOANN 1/20/06 @ 1 PM |
|
| 10/06/2005 | ELECTRIC - FINAL | Partial Approval | ||
| 10/06/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK FINAL |
|
| 10/03/2005 | ELECTRIC - FINAL | Denied | FINISH ?? BUTTON 7 TIE IN EXTENDER RINGS ( TILE) FINISH LOBBY CABINET & INSTALL RECEPTACLE |
|
| 09/29/2005 | ELECTRIC - FINAL | Partial Approval | BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 CANNOT SUPPORT OFF OF COPPER PIPES FIXTURES TO BE ATTACHED TO GRID 410.16 BOND EXHAUST FAN ENCLOSURE. NOT UNDER A MOUNTING SCREW. STRAP 2" FLEX CONDUIT FILL UNUSED OPENINGS TOP PANEL "EP-2" SUPPORT WIRES TO BE AS PER 300.11 ATTACHED BOTH ENDS FINISH ELECTRIC. IVRS - Inspection :* |
|
| 09/18/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 08/26/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DISCUSSED CLEARANCE ISSUE IN ELECTRIC EQUIPMENT ROOM AND RELOCATION OF EXISTING ELECTRIC EQUIPMENT |