Permit: T05CM00939

Parcel: 110121000


Addresses:

5140 E GLENN ST

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
11/07/2005 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
11/03/2005 ELECTRIC - UNDERGROUND Not ready for Inspection WHERE IS DISCONNECTING MEANS FOR WALK IN BOX-CORD NOT ALLOWED FOR PERMANENT WIRING METHOD OR ABOVE CEILING. BOX FILL MAY BE A CONCERN.
SECURE VDV CABLES TO BOX AND FILL UNUSED OPENING-AN APPROVED FITTING IS NEEDED'
MAINTAIN WORKING CLEARANCE IN ELECTRIC ROOM AT ALL TIMES ROOM IS NOT A STORE ROOM
PROTECT SEAL TITE FROM SHARP METAL EDGES AND TIGHTEN LOOSE FITTINGS-FINISH LAST UNIT-LABEL UNITS
FINISH # 8 PREVIOUS INSPECTION
RECEIVED LETTER FOR ?? LIGHTS
11/01/2005 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*RICK H WILL NEED TO SIGN THIS INSPECTION( HE WAS NOT AVAILABLE TO INSPECT THIS TODAY DUE TO CLASSES ON TUES & WEDS
10/26/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK CEILING TILES IN NON ESENTIAL TO ELECTRIC AREAS
2) WIRING METHODS TO MEDICAL LIGHTS TO BE AS PER 517.13 OR PROVIDE LETTER FOR NON PATIENT USAGE
3) IDENTIFY ALL CONDUCTORS
4) BOXES MORE THAN 1/4" IN NON COMBUSTIBLES TO USE AN APPROVED EXTENDER RING
5) TIGHTEN LOOSE SEAL TITE FITTINGS
6) A. BOND BUSHING IS NEEDED FOR CONCENTRICS OVER 250V 250.97
7) VERIFY LISTING AND LABEL WASHER DRYER
8) VDV CABELING TO BE AS PER 725.6 AND 800.6, 760.6
9) NEED SUPPORTS FOR M/C CABLES FROM JUNCTION BOXES
10) SHEET METAL SCREWS NOT ALLOWED FOR BONDING
09/20/2005 ELECTRIC - UNDERGROUND Partial Approval
07/25/2005 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
1) NOT READY INSPECTED ON 7/22/05
07/22/2005 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) OK 8 FLOOR BOXES AND PVC CONDUIT