Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2005 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 11/03/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | WHERE IS DISCONNECTING MEANS FOR WALK IN BOX-CORD NOT ALLOWED FOR PERMANENT WIRING METHOD OR ABOVE CEILING. BOX FILL MAY BE A CONCERN. SECURE VDV CABLES TO BOX AND FILL UNUSED OPENING-AN APPROVED FITTING IS NEEDED' MAINTAIN WORKING CLEARANCE IN ELECTRIC ROOM AT ALL TIMES ROOM IS NOT A STORE ROOM PROTECT SEAL TITE FROM SHARP METAL EDGES AND TIGHTEN LOOSE FITTINGS-FINISH LAST UNIT-LABEL UNITS FINISH # 8 PREVIOUS INSPECTION RECEIVED LETTER FOR ?? LIGHTS |
|
| 11/01/2005 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999*RICK H WILL NEED TO SIGN THIS INSPECTION( HE WAS NOT AVAILABLE TO INSPECT THIS TODAY DUE TO CLASSES ON TUES & WEDS |
|
| 10/26/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK CEILING TILES IN NON ESENTIAL TO ELECTRIC AREAS 2) WIRING METHODS TO MEDICAL LIGHTS TO BE AS PER 517.13 OR PROVIDE LETTER FOR NON PATIENT USAGE 3) IDENTIFY ALL CONDUCTORS 4) BOXES MORE THAN 1/4" IN NON COMBUSTIBLES TO USE AN APPROVED EXTENDER RING 5) TIGHTEN LOOSE SEAL TITE FITTINGS 6) A. BOND BUSHING IS NEEDED FOR CONCENTRICS OVER 250V 250.97 7) VERIFY LISTING AND LABEL WASHER DRYER 8) VDV CABELING TO BE AS PER 725.6 AND 800.6, 760.6 9) NEED SUPPORTS FOR M/C CABLES FROM JUNCTION BOXES 10) SHEET METAL SCREWS NOT ALLOWED FOR BONDING |
|
| 09/20/2005 | ELECTRIC - UNDERGROUND | Partial Approval | ||
| 07/25/2005 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY INSPECTED ON 7/22/05 |
|
| 07/22/2005 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK 8 FLOOR BOXES AND PVC CONDUIT |