Permit: T05CM00933

Parcel: 124161400


Addresses:

835 E 22ND ST

Inspection Status: Partial Approval

Inspection History: ELECTRIC - PROGRESS

Date Description Inspector Results Comments
12/27/2006 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. INSTALL PLASTER RINGS
2. INSTALL SEALS IN HOLES
3. GROUND ALL METAL BOXES
12/27/2006 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
10/26/2006 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
10/20/2006 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. CABLES MUST HAVE 1 1/4" MIN. SPACE BETWEEN FACE OF STUD TO CABLES TO PREVENT DAMAGE FROM SCREWS,
PER NEC. 300.4 USE NAIL PLATES WHERE APPLICABLE.
2. IT WILL BE NECESSARY TO DE-RATE AMPACITY FOR CABLES BUNDLED TOGETHER IN LENGHTS MORE THAN 2' --
300.15 B NEC
3. PROVIDE LETTER FROM ARCH. FOR APPROVAL OF MC INSTEAD OF CONDUIT.