Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2006 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. INSTALL PLASTER RINGS 2. INSTALL SEALS IN HOLES 3. GROUND ALL METAL BOXES |
|
| 12/27/2006 | ELECTRIC - PROGRESS | Approved | IVRS - Inspection :* | |
| 10/26/2006 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* | |
| 10/20/2006 | ELECTRIC - PROGRESS | Partial Approval | IVRS - Inspection :* 1. CABLES MUST HAVE 1 1/4" MIN. SPACE BETWEEN FACE OF STUD TO CABLES TO PREVENT DAMAGE FROM SCREWS, PER NEC. 300.4 USE NAIL PLATES WHERE APPLICABLE. 2. IT WILL BE NECESSARY TO DE-RATE AMPACITY FOR CABLES BUNDLED TOGETHER IN LENGHTS MORE THAN 2' -- 300.15 B NEC 3. PROVIDE LETTER FROM ARCH. FOR APPROVAL OF MC INSTEAD OF CONDUIT. |