Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM00931
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 04/28/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OVERHANG LESS THAN 3' TO P/L WILL NEED TO BE FIRERATED 2) ITEMS 1, 2, 3, 4, 5 AND 8 INCOMPLETE |
|
| 04/22/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL TRUSS X BRACE MAX 25' OF RUN EXT. WIND BRACING SAME 2) INSTALL BANG PLATES EXTERIOR BOTTOM PLATES AT PLUMBING CUTS 3) 2 NAILS REQUIRED TOP AND BOTTOM WIND BRACING 4) 6 HOLDOWNS MISSING REAR 5) MISSING HOLDOWN GARAGE AT BEDROOM #3/OFFICE AND OSB SHEARWALL 6) STAPLES STICKING UP ON ROOF 7) MISSING HOLDOWNS EACH SIDE GARAGE DOOR OPENING 8) GARAGE SHEAR AT 8' HEIGHT NOT NAILED TO SAME TOP PLATE FOR CONTINOUS TRANSFER AND INSTALL NAILERS ON THAT GABLE TRUSS SO AS TO NAIL SHEAR AT 16" CENTERS 9) STOPPED INSPECTION |