Permit: T05CM00898

Parcel: 140376130


Addresses:

6895 S GOSHAWK DR

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/08/2005 FRAMING Approved IVRS - Inspection :*
07/06/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) STUCCO CORNER REINFORCING NOT INSTALLED. 2) LSL NOT NAILED PER PLAN. 3) NAIL PROTECT WIRES. 4) HIP HANGER NOT NAILED. 5) P-3 REQUIRES 12 A35S. 6) HOLD DOWN MUST BE HTT16 LTT20 INSTALLED. 7 ) P-3 SHEAR WALL REQUIRES PINS AT 3" O.C. 8) F-2 TRUSS HEADER MUST BEAR ON HANGER. 9) SECURE WIRES WITHIN 8" OF ELECTRIC BOXES. 10. MAKE UP ALL GROUND WIRES. 11) BLOCK MECHANICAL BOOTS 3 SIDES. 12) FIRE BLOCK W/H VENT. 13) STAIRS HAVE MORE THAN 3/8" RISE DIFFERENCE. 14) NAIL SECOND FLOOR SHEAR WALL PLATE TO FLOOR PER PLAN.